OVERVIEW


The ATC-900 C9ontroller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.

The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-800 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.

BENEFITS

Product Features

True rms three-phase voltage sensing on Source 1, Source 2 and loadFrequency sensing on Source 1 and Source 2Preferred source selection Programmable set points stored in nonvolatile memory Modbus communication to personal computer either on site or remote Viewable historical data on the most recent transfers (up to 16 events) are viewable at switch. Unlimited history storage (remote) available when used with remote softwareLoad sequencing (optional)Engine start contacts (2 sets) Engine test switch with user-selectable test mode and fail-safeAlarm contact (multiple alarm functions available) Pretransfer signal (optional) Heartbeat monitor (flashing light signifies that the ATC-800 is operating properly)Instrumentation:Voltmeter (accuracy ±1%)Reads line-to-line on Sources 1 and 2 and load Frequency meter (40–80 Hz, accuracy ±0.1 Hz)Source available time (both sources)Source available time (both sources)

ATC-800 Programming

Buttons provide easy access to all commonly used ATC-800 functions. When Source 1 is connected and the ATS is operating normally, the automatic indicator light will be flashing and the display window will be blank.Using the Display Select button, the operator can step through each of the six display families: Source 1 Source 2 Load History Time/Date Set Points

Initial Programming

Factory programming will load all standard features and customer-specified options per the default settings.

Customer Programing

Customers may reprogram set points and other parameters to match their application using the Program switch located on the rear of the unit. Once the programming mode has been activated and the Program light is flashing, the user may access Set Point settings by pressing the Display Select button until the Set Points LED is illuminated.Values for individual set points may then be altered by pressing the Increase (arrow up) or Decrease (arrow down) buttons. Once a parameter has been reset, the user advances to the next set point by pressing the Step button. While the ATC-800 is in the Program mode, the device continues to operate in accordance with the previously programmed set points and parameters. The unit is never offline and preset values do not change until programming has been completed. Once reprogramming is complete, the user may return the Program switch to the Run position. At this point, all new values are stored in the ATC-800 nonvolatile memory and the unit returns to Automatic mode.

Open Transition / In Phase Monitor

In-phase monitor is a feature that will allow a transfer between two sources only when the phase difference between the two sources is near zero. This is an open transition transfer that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.

Open Transition / Delayed with Load voltage

Load voltage decay transfer is a feature that, after opening the switch for the original source, holds in the neutral position until the voltage on the load is less than 30% of rated voltage. This operation is an open transition that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.

Operation

The Cat ATC-800 transfer operates in the following modes:Loss of normal powerOpen transition to alternate source Normal power restored Open transition back to normal source Test (user selectable) Load transfer—open transition to and from alternate source No-load transfer—starts alternate power source and allows to run unloaded; no transfer takes place

Applicable Testing

UL Recognized ComponentMeets Seismic Requirements of Uniform and CBC 2007 and IBC 2006 (exceeding requirements of worst case Zone 4 levelsComplies with UL 991 environmental testsComplies with IEC 61000-4-2, 61000-4-3,61000-4-4,and 61000-4-5Complies with CISPR 11, Class AComplies with CSA 22.2-178Complies with FCC Part 15, Subpart B, Class A

ATC-900 CONTROLLER

Get a Quote for ATC-900 CONTROLLER

Thank you! One of our specialists will be in contact soon.
It looks like something went wrong. Please check fields and submit form again.

BROWSE

SIMILAR EQUIPMENT

SUBSCRIBE

Never miss out on the latest news & specials when you subscribe to Ohio CAT® marketing updates

Thank you! One of our specialists will be in contact soon.
It looks like something went wrong. Please check fields and submit form again.

THANK YOU!

Lorem ipsum dolor sit amet, consectetur adipiscing elit, sed do eiusmod

DONE